News Release
U.S. Environmental Protection Agency
New England Regional Office
January 9, 2013
U.S. Environmental Protection Agency
New England Regional Office
January 9, 2013
Contact: David Deegan, (617)
918-1017
Company to Pay Fine for Chemical Accident
Prevention Violations in
Sandwich, Mass. and E. Providence, R.I.
(Boston, Mass. – Jan. 9, 2013) – A cold
storage and ice manufacturing company has agreed to pay penalties of $225,000 to
settle claims by EPA that the company violated federal Clean Air Act
requirements meant to prevent chemical releases relating to its use of ammonia
at facilities located in East Providence, R.I., and Sandwich, Mass.
According to EPA’s complaint, JP Lillis
Enterprises, which does business under the trade name Cape Cod Ice, failed to
put in place a required “Risk Management Plan” for ammonia used in the
refrigeration system at its East Providence facility, in violation of the
federal Clean Air Act. EPA also alleged that the company violated the Clean Air
Act’s General Duty Clause, which applies to facilities where extremely hazardous
substances such as ammonia are present, at its Sandwich location.
Under the General Duty Clause, owners and
operators of these facilities are required to identify hazards, design and
maintain the facility in a safe manner, taking steps to prevent accidental
releases of the extremely hazardous substance, and take steps to minimize the
consequences of any accidental releases that occur. The company had not taken
required steps to design and maintain a safe facility or taken precautions that
would minimize the consequences of an accidental release of ammonia, if one were
to occur, at its Sandwich facility. For example, they failed to provide
mechanical ventilation; working ammonia detectors and an emergency shutdown
switch for the machinery room; develop operating procedures and a comprehensive
mechanical integrity program; and train employees in the proper operation of the
system at the Sandwich facility.
Ammonia presents a significant health hazard
because it is corrosive to the skin, eyes and lungs. Exposure to 300 parts per
million is immediately dangerous to life and health. Ammonia is also flammable
at concentrations of about 15 to 28 percent by volume in air. It can explode if
it is released in an enclosed space with a source of ignition present, or if a
vessel containing anhydrous
ammonia is exposed to fire.Risk Management Plans required under the Clean Air Act, and steps required under the General Duty Clause, help prevent accidental releases of substances that can cause serious harm to the public and the environment from short-term exposures and reduces the severity of releases that do occur. A company that fails to take these steps can leave the public and environment at risk from accidental releases.
Both Cape Cod Ice facilities are located less
than a fifth of a mile from residential homes, and less than a quarter of a mile
from retail and office areas.
This case stems from information learned about
JP’s facilities following an inspection of the Sandwich facility by EPA in
November 2011. After EPA’s inspection, JP developed and submitted a risk
management plan for its East Providence facility, and the company is currently
working to fix problems identified at the Sandwich facility. For example, the
company has installed an ammonia detector at the Sandwich Facility and
investigated and corrected pipe corrosion and vibration problems noted by EPA
inspectors. JP also plans to install a ventilation fan and an emergency
shutdown switch and to prepare and implement an improved maintenance program for
the system.
More information: General Duty Clause and
Risk Management Plans (http://www.epa.gov/compliance/monitoring/programs/caa/112r.html)
# #
#
No comments: